Reclaimed Water Reuse Rate: At the Same Plant, Both 99% and 16.7% Are Correct — What Differs Is the Denominator
The previous article discussed mixing, where what got replaced was power; this article discusses reclaimed water reuse, where what gets replaced is the denominator. Appendix B of GB/T 7119 provides four formulas, with four denominators falling in four different positions—three are water quantities (only the stream of water selected differs), and the fourth is not a water quantity at all, but steam production. For the same plant and the same batch of water meters, 99.0%, 95.3%, 40.0%, and 16.7% can all be calculated. And as soon as the reuse rate is pushed upward, it immediately hits three walls: the ceiling on the concentration ratio is actually wind drift loss; when the chloride ion concentration of make-up water is close to the upper limit of 250, the two national standards multiplied together have no solution; the upper limit of the plant-wide reuse rate is influent salt divided by effluent salt, and has nothing whatsoever to do with the membrane recovery rate.
I. Five denominators: four are hidden in one standard's appendix
GB/T 7119—2018 "Guidelines for Evaluation of Water-Saving Enterprises," Appendix B, is the most honest appendix this series has seen—it lays out the formulas for four "rates" side by side, which is equivalent to admitting that there is no single denominator for this matter.
| Indicator | Formula | What the denominator is | Value used in this calculation example |
|---|---|---|---|
| Reuse rate R (B.2, same formula as B.10) | R = Vr / (Vi + Vr) × 100% | Water intake + reused water volume | 122 000/128 000 = 95.3% |
| Direct cooling water circulation rate Rd (B.3) | Rd = Vdr / (Vdf + Vdr) × 100% | Direct cooling make-up water + direct cooling circulation volume | No direct cooling at this plant; not applicable |
| Indirect cooling water circulation rate Rc (B.4) | Rc = Vcr / (Vcf + Vcr) × 100% | Indirect cooling make-up water + indirect cooling circulation volume | 120 000/121 200 = 99.0% |
| Steam condensate reuse rate Rb (B.5) | Rb = Vbr / D × ρ × 100% | Steam generation × density (not water volume!) | 1 000/1 100 = 90.9% |
| Industrial water reuse rate Rw (B.10) | Rw = Vr / (V + Vr) × 100% | Water intake + reused water volume | 122 000/128 000 = 95.3% |
| Wastewater reuse rate (common industry basis) | Reused wastewater volume / total wastewater generated | Wastewater generation volume | 1 000/2 500 = 40.0% |
Two things in this table are worth highlighting separately.
First, B.2 and B.10 are the same formula. The former is called "reuse rate", with the symbol Vr/(Vi+Vr); the latter is called "industrial water reuse rate", with the symbol Vr/(V+Vr). The textual descriptions of the denominators are also almost identical, except that B.10 defines the water intake scope in more detail (including main production, auxiliary production, and ancillary production; excluding construction, firefighting, and external supply). In Table 1, these two rows calculate the same 95.3%. It is not that I double-counted; they are simply the same formula written twice. In the same appendix of the same standard, giving the same indicator two numbers and two sets of symbols usually means that different people drafted different sections and the drafts were never merged. When citing, choose one.
Second, the denominator of B.5 is not a water volume. The steam condensate reuse rate is written as Rb = Vbr/D×ρ, where D is the steam generation rate (t/h), and only after multiplying by density does it become a volume. This means the condensate reuse rate inherently carries an assumption: one ton of steam corresponds to one ton of water. For plants with large amounts of extraction steam, exhaust steam, and temperature/pressure reduction, this assumption makes the denominator smaller and the reuse rate look better. Whenever you see "condensate reuse rate above 95%" without a stated basis for steam generation, first ask: does D include extraction steam?

II. The numerator is not clean either: which column is purchased reclaimed water recorded in
Once the denominator is clear, the numerator still involves a choice. The 1 000 m³/d that an enterprise buys from a municipal reclaimed water plant—under the GB/T 7119 system, is it counted as "water intake Vi" or as "reused water volume Vr"?
Both accounting methods are defensible. Count it as water intake: it is water obtained from outside, requiring a water intake permit and payment of a water resource tax. Count it as reuse: it replaces fresh water and is a water-saving achievement.
In this calculation example, if 1 000 m³/d is recorded as water intake: Vi = 7 000, Vr = 121 000, Rw = 121 000/128 000 = 94.5%; if recorded as reuse: Vi = 6 000, Vr = 122 000, Rw = 122 000/128 000 = 95.3%.The same water stream and the same total water use, 0.8 percentage points. Note that the total 128 000 has not changed—that water stream has merely moved from one column to another, but it determines whether the number on the report matches the number in the water intake permit ledger. As for someone calculating "reuse volume ÷ water intake" as 16.7% and also calling it a reuse rate, that is a fifth denominator and is not among the four formulas in GB/T 7119.
This is not a word game. The water intake permit ledger, water resource tax declaration, water-saving enterprise evaluation, and carbon emission accounting—these four tables may record this water stream differently, and the four tables will not automatically reconcile with one another. Whenever an enterprise's "reuse rate 95%" does not match its "water intake per unit product", the first thing to ask is which column the purchased reclaimed water is recorded in.
III. From "rate" to "ratio": three formulas, one division
The reuse rate is a bookkeeping matter; the concentration ratio is an operational matter. In a circulating cooling water system, these two numbers are linked by one division, and that division is rarely written out.
Clause 3.1.11 of GB/T 50050—2017 gives the definition formula for the concentration ratio (symbols follow the specification):
N = Qm /(Qb + Qw)
where Qm is the makeup water volume, Qb is the blowdown water volume, and Qw is the wind drift loss water volume. Evaporation loss Qe is not in the denominator—because it does not carry salts away. Substituting Qm = Qe + Qb + Qw and rearranging gives:
Qm = Qe · N /(N − 1) Qb = Qe /(N − 1) − Qw
The first formula is the makeup water formula that appears repeatedly in various environmental impact assessment reports (together with Qe = k·Δt·Qr, with k taken as 0.0015/℃). The second formula is rarely seen, but it is the key: blowdown volume equals "evaporation volume divided by N−1", minus wind drift loss. Normalizing with evaporation volume as 1 gives Table 2.
| Concentration Ratio N | Makeup Water Qm/Qe | Blowdown Qb/Qe | Blowdown-to-Makeup Ratio (= 1/N) |
|---|---|---|---|
| 2.0 | 2.000 | 1.000 | 50.0% |
| 2.5 | 1.667 | 0.667 | 40.0% |
| 3.0 | 1.500 | 0.500 | 33.3% |
| 3.5 | 1.400 | 0.400 | 28.6% |
| 4.0 | 1.333 | 0.333 | 25.0% |
| 5.0 | 1.250 | 0.250 | 20.0% |
| 6.0 | 1.200 | 0.200 | 16.7% |
| 8.0 | 1.143 | 0.143 | 12.5% |
| 10.0 | 1.111 | 0.111 | 10.0% |
From N=3 to N=5: makeup water drops from 1.500 to 1.250, a decrease of 16.7%; blowdown drops from 0.500 to 0.250, a decrease of 50%. From N=5 further to N=10: makeup water decreases by another 11.1%, and blowdown by another 55.6%.
IV. The Ceiling Is Not Scale, It Is Wind Drift
The minus sign in the second equation conceals a physical upper limit. Let Qb = 0:
Nmax = 1 + Qe / Qw
That is, when the concentration ratio is high enough that "evaporation divided by N−1" exactly equals the wind drift loss, the blowdown volume is zero and the system can no longer concentrate further. This is not a scaling limit, not a chemical limit, but an arithmetic limit of water volume: the water carried away by wind drift does not participate in concentration, but it must first be deducted from the makeup water account.
Calculated at Qe = 1.5% circulating water volume (k=0.0015/℃, Δt=10 ℃):
- Wind drift loss 0.10% (newer towers, high-efficiency drift eliminators): Qe/Qw = 15, Nmax = 16;
- Wind drift loss 0.30%: Qe/Qw = 5, Nmax = 6;
- Wind drift loss 0.35% (common in old towers): Qe/Qw = 4.29, Nmax = 5.3.
The last row deserves a pause. For an old tower, the blowdown volume reaches zero at N≈5.3, while the upper limit given by GB/T 50050 is exactly 5.0.The difference between the code upper limit and the physical limit of an old tower is only a factor of 0.3—this is no coincidence; this account was already calculated when the code values were set. Conversely: if a tower's wind drift loss reaches 0.5%, its physical ceiling is 4.0, and at that point "raising to 5 times" is impossible on this tower, no matter how good the water quality or how strong the chemicals.

V. The Chloride Chain: Two National Standards Multiplied Together Have No Solution
The water quality side has harder limits than the water volume side, because it can be back-solved to a specific number.
The upstream is GB/T 19923—2024 "Urban Sewage Reuse—Water Quality for Industrial Use" Table 1: when used as makeup water for indirect open circulating cooling water, chloride ≤ 250 mg/L. The downstream is GB/T 50050—2017 Table 3.1.7: for indirect open circulating cooling water systems, chloride ≤ 1000 mg/L (water in tube side, carbon steel or stainless steel heat exchange equipment), ≤ 700 mg/L (water in shell side, stainless steel heat exchange equipment, heat transfer surface wall temperature ≤70 ℃ and cooling water outlet temperature <45 ℃).
Chloride hardly volatilizes, does not deposit, and is not biologically utilized, so its concentration in circulating water is approximately equal to the makeup water concentration multiplied by the concentration ratio. Connecting the two standards:
Ccirculating = Cmakeup × N
Substituting 250 and 700: N ≤ 700/250 = 2.8. Yet GB/T 50050 Clause 3.1.11 requires that for indirect open systems the concentration ratio should not be less than 3.0.
What about a different type of heat exchanger? At the 1000 mg/L tier, 250×N=1000 gives N=4.0, which falls within the 3.0~5.0 range and is usable. So the conclusion of this chain is not "reclaimed water cannot be used as cooling make-up water," but rather: when reclaimed water is used as cooling make-up water, the heat exchanger's structure and materials determine whether the cycles of concentration can hold, and this is often glossed over in the feasibility study stage as merely "water quality meets standards."
The next tier down is even more severe. Existing project reports record: a certain 300 MW cogeneration unit using municipal reclaimed water as make-up water, maintaining cycles of concentration at 3.0~3.5, with circulating water chloride reaching 750~875 mg/L; the condenser's 304 stainless steel tube bundle developed pitting perforation in the 14th month of operation, and 17 tubes were plugged. The chloride control value for 304 stainless steel under cold water conditions is generally taken as 200 mg/L—solving backward from this number, 250×N ≤ 200 gives N ≤ 0.8, which cannot even achieve one cycle of concentration. This chain is completely broken for 304 materials.
Laboratory data pins the threshold down one more layer. Using 316L stainless steel as the subject and water samples at 3 times reclaimed water concentration: when chloride exceeds 380 mg/L, erosion of the passive film intensifies markedly, with anodic dissolution current density reaching up to 2.11 μA/cm²; when ammonia nitrogen exceeds 15 mg/L, it likewise intensifies, reaching up to 1.01 μA/cm²; when sulfate reaches 520 mg/L (at which point the chloride/sulfate ratio is 0.54), the erosion is effectively mitigated, with the anodic dissolution current density dropping by up to 59.0%.What the three numbers together mean is: chloride does not act alone—it has an opponent (sulfate) and an accomplice (ammonia nitrogen), and GB/T 19923—2024 happens to tighten ammonia nitrogen from 10 to 5 and set sulfate by category at 250/600.

VI. Standard Revision: From One Column to Two, Two Opposite Directions
GB/T 19923—2024 was implemented on 2024 年 10 月 1 日, replacing the 2005 version. The most easily overlooked action in this revision is splitting the original single table into two columns: one column is "make-up water for indirect open circulating cooling water, boiler feed water, process water, product water," and the other is "once-through cooling water, washing water." The same standard, two types of users, opposite directions.
| Item | 2005 Edition (Single Column) | 2024 Edition Column 1 Indirect Cooling Make-up Water / Boiler Feedwater / Process and Product Water | 2024 Edition Column 2 Once-through Cooling / Washing Water |
|---|---|---|---|
| pH | 6.5~8.5 | 6.0~9.0 | 6.0~9.0 |
| Color / degree | 30 | 20 | 20 |
| Turbidity / NTU | 5 | 5 | — |
| BOD5 / (mg/L) | 10 | 10 | 10 |
| COD / (mg/L) | 60 | 50 | 50 |
| Ammonia Nitrogen (as N) | 10 | 5 (copper alloy heat exchanger <1) | 5 |
| Total Nitrogen (as N) | Not specified | 15 | 15 |
| Total Phosphorus (as P) | 1 | 0.5 | 0.5 |
| Total Hardness (as CaCO3) | 450 | 450 | 450 |
| Total Dissolved Solids | 1000 | 1000 | 1500 |
| Chloride | 250 | 250 | 400 |
| Sulfate | 250 | 250 | 600 |
| Iron / Manganese | 0.3 / 0.1 | 0.3 / 0.1 | 0.5 / 0.2 |
| Silica | 30 | 30 | 50 |
| Suspended Solids | 30 | Deleted (controlled by turbidity) | Deleted |
| Fecal Coliform / (MPN/L) | 2000 | 1000 | 1000 |
| Total Residual Chlorine / (mg/L) | ≥0.05 | 0.1~0.2 | 0.1~0.2 |
| Fluoride / Sulfide | Not specified | 2.0 / 1.0 (optional control items) | 2.0 / 1.0 |
For plants using indirect cooling make-up water, this is an overall tightening: COD 60→50, ammonia nitrogen 10→5, total phosphorus 1→0.5, color 30→20, fecal coliform 2000→1000, and residual chlorine changes from a single lower limit to a range. For plants using washing water and once-through cooling, this is a relaxation: TDS is set at 1500, chloride 400, sulfate 600, iron and manganese doubled, silica 50, and turbidity is simply not specified.
Seven, the four characters "boiler make-up water" refer to raw water, not feedwater
The most error-prone cell in Table 1 and Table 3 is where "boiler make-up water" and "indirect cooling open-circuit make-up water" share the same column, with total hardness both at 450 mg/L.
450 mg/L (calculated as CaCO3) converted to hardness is 4.5 mmol/L. Meanwhile, GB/T 1576—2018 "Water Quality for Industrial Boilers" requires, for natural circulation steam boilers using external water treatment, a feedwater hardness of ≤0.03 mmol/L (with softened water make-up), tightened to ≤5×10⁻³ mmol/L when supplied with demineralized water. The difference between the two is 150 times.
The gap is not standards conflicting; it is different sampling points: GB/T 19923 governs "industrial water raw water" — it is the water entering the plant, followed by a water treatment system; GB/T 1576 governs "feedwater" — water already treated and ready to enter the boiler. Those two characters in the title are qualifiers, not modifiers.
But on site, some indeed use the former as the latter. The criterion is simple: if 450 mg/L were the boiler feedwater standard, then no softener would ever need to exist.
Incidentally, let us also clarify the position of the double-membrane process. With primary RO desalination rate at 98% and influent hardness at 450 mg/L, the permeate is about 9 mg/L, i.e. 0.09 mmol/L — still three times 0.03; at 99% it is about 4.5 mg/L, i.e. 0.045 mmol/L, still 1.5 times.
Eight, the double-membrane process does not make water cleaner; it switches columns
Putting the previous sections together, the role of the double-membrane process in Reclaimed Water Reuse can be stated in one sentence: it does not change the "cleanliness" of the water; it changes which column of Table 3 the water can enter.
The effluent of the conventional "three-stage" process (coagulation—sedimentation—filtration) has turbidity 3~5 NTU, TDS 800~1200, chloride 150~250, hardness 250~400, and can only stably enter column 2 (once-through cooling, washing); to achieve column 1 indirect cooling make-up, one must look at the make-up water background; and once the chloride in column 1 approaches 250, as calculated in Section Five, N≥3 cannot hold.
The effluent indicators of the double-membrane process are on another level: Ultrafiltration / UF permeate turbidity <0.2 NTU, SDI15 <3 (this is the threshold for RO influent, not a product specification); Reverse Osmosis / RO permeate TDS 20~100 mg/L, conductivity <150 μS/cm, hardness 2~5 mg/L. Chloride can be suppressed below 20 mg/L — back-solving along the chain in Section Five, when make-up water chloride is 20 mg/L, N=5 only reaches 100 mg/L, a factor of 700 short of 7, and the ceiling of the concentration ratio is handed back to wind drift losses and scaling.
| Route | Effluent Turbidity / SDI | Effluent Salt Content | System Recovery Rate | Applicable Categories | Main Bottlenecks |
|---|---|---|---|---|---|
| Conventional Three-Stage (Coagulation + Sedimentation + Filtration) | 3~5 NTU | TDS at the same order of magnitude as influent | — (no desalination) | Category 2 Once-through Cooling / Washing | Salt content not reduced; Category 1 depends on background level |
| MBR + RO | Turbidity <1 NTU | TDS 50~150 | 60~75% | Category 1 | Severe membrane fouling, high aeration energy consumption |
| UF + RO (Dual-Membrane Process) | UF <0.2 NTU, SDI15 <3 | TDS 20~150, conductivity <150 μS/cm | 70~80% | Category 1 (including raw water for boiler make-up water) | Concentrate disposal, pretreatment stability |
| UF + RO + DTRO/High-Pressure RO | Same as Dual-Membrane Process | Permeate same as Dual-Membrane Process; concentrate TDS up to 120~150 g/L | 85~90% (overall) | Category 1 + Near-Zero Liquid Discharge | High pressure, energy consumption, concentrate solidification |
IX. Salt Balance: For Every Five Points of Recovery Rate, Concentrate Concentration Rises by 25%
The membrane recovery rate Y and the concentrate concentration factor CF are two ways of expressing the same number. Neglecting the small amount of salt carried away by the permeate:
CF = 1 / (1 − Y)
| Recovery Rate Y | Concentrate Fraction 1−Y | Concentration Factor CF | Concentrate TDS / (mg/L) |
|---|---|---|---|
| 50% | 50% | 2.00 | 2 000 |
| 60% | 40% | 2.50 | 2 500 |
| 70% | 30% | 3.33 | 3 333 |
| 75% | 25% | 4.00 | 4 000 |
| 80% | 20% | 5.00 | 5 000 |
| 85% | 15% | 6.67 | 6 667 |
| 90% | 10% | 10.00 | 10 000 |
From 75% to 80%: permeate increases by 5 points and concentrate decreases by 5 points, but the concentrate concentration rises from 4 000 to 5 000, an increase of 25%. The total amount of salt remains unchanged; it is simply squeezed into less water. This is why "recovery rate stuck at 75%" is so common in engineering practice—at 75%, the concentrate is exactly one quarter of the feedwater volume at four times the concentration, still within the operating window of conventional spiral-wound membranes; beyond that, concentration polarization at the membrane surface, osmotic pressure, and scaling risk all rise simultaneously.
10. The Plant-Wide Ceiling: Influent Salt Divided by Effluent Salt
The membrane recovery rate is a unit-level constraint; the plant-wide reuse rate has an even harder constraint stemming from the salt balance itself.
Let the plant-wide water intake be Vf with salt content Cf, and the discharge be Vb with salt content Cb. Salt can only leave with the water (ignoring the small amount carried away by solid waste):
Vf · Cf = Vb · Cb → Vb = Vf · Cf / Cb
Defining the reuse rate as "the proportion of fresh water saved relative to the water intake," i.e., R = 1 − Vb/Vf:
R ≤ 1 − Cf / Cb
| Influent salinity Cf | Permissible discharge salinity Cb | Cf/Cb | Upper limit of reuse rate |
|---|---|---|---|
| 300 mg/L | 2 000 mg/L | 0.15 | 85% |
| 500 mg/L | 2 000 mg/L | 0.25 | 75% |
| 1 000 mg/L | 2 000 mg/L | 0.50 | 50% |
| 1 500 mg/L | 2 000 mg/L | 0.75 | 25% |
| 500 mg/L | 1 000 mg/L | 0.50 | 50% |
The 75% in the second row is the same number as the "wastewater reuse rate stuck at 75%" that repeatedly appears in the industry. It is not a coincidence, nor is it the limit of the membrane—it is the ratio of "influent 500 mg/L divided by discharge permit 2 000 mg/L." To break through, there are only two paths: bring Cf down (add desalination upstream, which means moving the salt earlier, but the salt does not disappear—it merely becomes concentrate), or raise Cb (change the discharge destination, or turn the salt into solid waste). Both paths lead to the same place: the salt outlet.
XI. Four Real Projects, Four Different "Rates"
| Project | Scale and Process | Key Data |
|---|---|---|
| Shenmu Coal Chemical Energy Company Reverse Osmosis Concentrate Quality Improvement and Scale Reduction | 900 m³/d concentrate; equalization tank + high-density sedimentation + valveless filter + Ultrafiltration + raw water RO (recovery 75%) + concentrate RO (recovery 60%) | Product water TDS ≤100 mg/L, conductivity ≤300 μS/cm, hardness nearly zero; daily water cost savings 1 800 元; annual reduction of wastewater discharge 27 万 t; total investment 326 万 yuan, annual comprehensive savings 146 万 yuan, payback period less than 3 年 |
| A Paper Mill in Jiangsu Effluent Reuse | 7 000 m³/d; pre-filtration + Ultrafiltration + Reverse Osmosis | Ultrafiltration recovery 95%, flux 25 L/(m²·h); RO average salt rejection 97%, water recovery 75%, flux 24.79 L/(m²·h); system total recovery above 70%; product water conductivity 25~40 μS/cm, TDS 15~25 mg/L, total hardness 2~4 mg/L; discharge reduced by nearly 70% |
| An Electroplating Industrial Park in Guangdong (Phase I) | 500 m³/d; Ultrafiltration + RO + DTRO re-concentration | RO recovery 70%; DTRO concentrates the concentrate TDS from about 20 000 mg/L to 120~150 g/L, volume reduction 70%; final waste liquid <5%; product water conductivity <200 μS/cm; annual fresh water savings about 10 万 m³ (calculated at 300 d) |
| A Lithium Battery Material Plant in Inner Mongolia Zero Liquid Discharge | 7 200 m³/d; multi-media + Ultrafiltration + primary RO + high-density sedimentation softening + resin softening + secondary RO + high-pressure RO + evaporation salt separation | Influent conductivity about 2 000 μS/cm; primary RO water production rate ≥75%; single-stage recovery ≥70%; high-pressure RO concentrate conductivity up to 120 000 μS/cm; product water conductivity <150 μS/cm; system comprehensive recovery ≥85% |
Putting the four projects together, four different things can be read from them.
This Shenmu case is "an annual account made with 900 tons of water producing 27 万 tons." 27 万 t ÷ 900 t/d = 300 d, the daily figures check out. But 1 800 元/d × 300 d = 54 万 yuan, which differs from the reported "annual comprehensive savings of 146 万 yuan" by 92 万 yuan. The composition of this 92 万 yuan is not broken down in the report—according to the project description, it should come from the cost of reduced external discharge, a decrease in chemical dosage of 90%, and indirect benefits from liquid level control in the mine water clear water tank. This kind of "comprehensive savings" is very common in promotional language; when citing it, only the verifiable half should be quoted: daily water cost savings of 1 800 元, annual reduction of external discharge of 27 万 t.
The Jiangsu paper case is the best sample of "three recovery rates written side by side." Ultrafiltration 95%, Reverse Osmosis 75%, system 70% or above—all three numbers are correct, but only the third is "how much water this system can reuse." The first two are unit indicators. If someone treats 95% as the system recovery rate, the concentrate volume will be underestimated by four times.
The electroplating case confirms the 75% in Section 10. RO recovery rate 70%, adding DTRO to further reduce the concentrate by 70%, comprehensive reuse rate exceeds 75%, and the final waste liquid is less than 5%. The path is clear: if the unit recovery rate is not enough, add another membrane stage to keep shrinking the "water denominator." But the cost is that the concentrate TDS goes from 20 000 to 120~150 g/L—salt is pushed to 15 万 mg/L, and the only option next is evaporation.
The lithium battery case is the complete version of the "salt separation" route. Comprehensive recovery rate ≥85%, meaning 15% of the concentrate enters the evaporator; its conductivity is 120 000 μS/cm, on the same order as the DTRO concentrate of the electroplating project. Two different industries, two different process trains, ending at the same number—this is not a coincidence, it is the salt balance speaking.
Twelve, Key Parameters: A Checklist You Can Take to the Review Meeting
- Reporting "reuse rate" must report the denominator. GB/T 7119 Appendix B has four formulas, B.2 and B.10 are the same formula with two numbers. Any number lacking a denominator must not enter the comparison table.
- Whether purchased Reclaimed Water is recorded as water intake or as reuse differs by 0.8 percentage points in this calculation example; switching to the "reuse volume ÷ intake volume" basis can differ from the reuse rate by five times.
- Makeup water = evaporation × N/(N−1); blowdown = evaporation/(N−1) − wind drift loss. The second formula is the truth about blowdown.
- Nmax = 1 + Qe/Qw. When wind drift is 0.1%, about 16; at 0.3%, about 6; at 0.35%, about 5.3. The condition of the drift eliminator directly determines the physical ceiling of the concentration ratio.
- Makeup water chloride upper limit = circulating water limit ÷ N. N=3 corresponds to 233 mg/L, N=5 corresponds to 140 mg/L, both lower than the 250 of GB/T 19923. When the heat exchanger is shell-side stainless steel (700), N≥3 and makeup water 250 cannot both hold.
- Material grades: carbon steel/stainless steel water in tube side 1000; stainless steel shell side, wall temperature ≤70 ℃, outlet water <45 ℃ take 700; 304 stainless steel cold water conditions are often controlled at 200 in engineering, at which point the N upper limit is less than 1.
- GB/T 19923—2024 is a two-column system. Column 1 (indirect cooling makeup water/boiler makeup water/process and product water) is tight, column 2 (once-through cooling/washing) is loose. For compliance judgment, first see which column the water enters.
- Boiler feedwater hardness 0.03 mmol/L (softened)/0.005 mmol/L (demineralized), differing from the 450 mg/L in Table 1 by 150 times, because one is feedwater and the other is raw water. Primary RO permeate is about 0.045~0.09 mmol/L, right at the question of "whether to add another stage."
- RO concentration factor CF = 1/(1−Y). When Y=75%, CF=4; when raised to 80%, CF=5, and the concentrate concentration rises by 25%.
- Plant-wide reuse rate upper limit = 1 − Cf/Cb. Independent of the process route. To break through, first answer where the salt goes.
Conclusion: Three Numbers, Three Things That Get Replaced
This article covers three layers, and each layer is the same action—replace something, then see what the number becomes.
The first layer replaces the denominator: for the same stream of water, the denominator changes from "intake + reuse" to "steam production × density" and then to "wastewater generation," and both 99.0% and 16.7% are true.
The second layer changes the location: chloride at the make-up water inlet is 250 and therefore compliant, but in the circulating water it is 750 and therefore exceeds the limit; the same 450 mg/L is qualified in the "raw water" column but falls short by a factor of 150 in the "feed water" column. The standard governs a certain cross-section, not the entire water path.
The third layer changes the carrier: water can be reused, salt cannot. For every percentage point increase in the reuse rate, the salt circulates one more round in the system and must ultimately end up somewhere—concentrate, sludge, mixed salt, or the receiving water body. The ceiling of the plant-wide reuse rate is written there: 1 − Cf/Cb.
So when seeing a report of "reclaimed water reuse rate 95%", what is worth questioning is not that 95%, but three things: what the denominator is, where the salt goes, and what kind of water the remaining 5% is. The answers to these three questions determine whether this 95% is a replicable engineering project or a report that only holds up on paper.
References
- GB/T 19923—2024 "Reuse of Urban Recycling Water — Water Quality Standard for Industrial Uses", issued on 2024-03-15, implemented on 2024-10-01, Table 1, Table 2, Chapter 5.
- GB/T 19923—2005 "Reuse of Urban Recycling Water — Water Quality Standard for Industrial Uses" (superseded by the 2024 version), Table 1; the comparison before and after the standard replacement is compiled from publicly republished materials and the "Main Technical Changes" in the foreword of this standard.
- GB/T 50050—2017 "Code for Design of Industrial Circulating Cooling Water Treatment", Clause 3.1.7 and Table 3.1.7 (circulating cooling water quality indicators), Clause 3.1.10, Clause 3.1.11 (cycles of concentration), Clause 3.1.12 (microbiological control).
- GB/T 7119—2018 "Guidelines for Evaluation of Water-Saving Enterprises", Appendix B, Formulas (B.2), (B.3), (B.4), (B.5), (B.10).
- GB/T 1576—2018 "Water Quality for Industrial Boilers", Table 1 (feedwater quality for natural circulation steam boilers and combined steam-water boilers with external water treatment).
- GB 18918—2002 "Discharge Standard of Pollutants for Municipal Wastewater Treatment Plant", Class I pollutants and selected control items.
- Luo Jingyan, Wang Huizhen, Xu Ping, Zhang Yajun. Impact Assessment of Reclaimed Water Makeup on the Circulating Cooling Water System of a Thermal Power Plant. Beijing University of Civil Engineering and Architecture. — System water volume 4 万 m³, circulating water flow 6~10 万 m³/h, reclaimed water makeup 1 000~1 600 m³/h; cycles of concentration maintained at 2~2.5; stability index: river water 6.98 (corrosive), reclaimed water 7.54 (severely corrosive); turbidity concentration ratio 5.49, Total Phosphorus 5.04.
- Research on Reuse of Municipal Reclaimed Water as Circulating Cooling Water (dissertation). — Static coupon test and calcium carbonate deposition method; lime dosage 1.25 times the theoretical amount, with PFS 20 mg/L, the removal rates of hardness, alkalinity, SS, and COD were 25.86%, 40.00%, 77.39%, 39.98%, respectively.
- Research on the Corrosion Effect of Water Quality Factors in Reclaimed Water on Stainless Steel Pipes and Its Control (dissertation). — 316L; when the chloride ion concentration in circulating water concentrated 3 times was >380 mg/L, corrosion intensified, with a maximum anodic dissolution current density of 2.11 μA/cm²; when ammonia nitrogen was >15 mg/L, the maximum was 1.01 μA/cm²; when sulfate was 520 mg/L, the decrease was 59.0%.
- Research on Treatment of Papermaking Wastewater by Membrane Separation Technology. — A paper mill in Jiangsu 7 000 m³/d; Ultrafiltration recovery 95%, flux 25~26 L/(m²·h); RO desalination rate 97%, recovery 75%, flux 24.79 L/(m²·h); system recovery above 70%.
- Shaanxi Coal Group Shenmu Coal Chemical Energy Company. Promoting Reverse Osmosis Concentrate Technical Innovation with a "Profit-Making" Mindset. — 900 m³/d; raw water RO recovery 75%, concentrate RO recovery 60%; produced water TDS ≤100 mg/L, conductivity ≤300 μS/cm; investment 326 万 yuan; annual reduction of external discharge 27 万 t.
- Wastewater Reuse Project of an Electroplating Industrial Park in Guangdong (industry technical report). — 500 m³/d; UF + RO + DTRO; RO recovery 70%; DTRO concentrate TDS 120~150 g/L, volume reduction 70%; final waste liquid <5%; annual water saving about 10 万 m³.
- Zero Liquid Discharge Project for Wastewater from a Lithium Battery Material Plant in Inner Mongolia (enterprise case). — 7 200 m³/d; influent conductivity about 2 000 μS/cm; first-stage RO water production rate ≥75%, single-stage recovery ≥70%; high-pressure RO concentrate conductivity 120 000 μS/cm; overall recovery ≥85%.
- Advanced Treatment Technology for Cold Rolling Wastewater. — Ultrafiltration design recovery 92.5%, produced water SDI15 <3, flux 69 L/(m²·h); double-membrane process accidents mostly occur in the pretreatment stage.
- Equipment Selection for Reclaimed Water Reuse and Double-Membrane System Configuration (industry technical materials). — Ultrafiltration produced water turbidity <0.2 NTU, SDI <3, system recovery above 90%; RO desalination rate ≥98%, recovery 70%~90%, produced water conductivity <150 μS/cm.
- Condenser Corrosion Case of a 300 MW Cogeneration Unit with Reclaimed Water Makeup (industry technical report). — Cycles of concentration 3.0~3.5, circulating water chloride ion 750~875 mg/L; 304 tube bundle suffered pitting perforation in the 14th month, with 17 tubes plugged.
- Interpretation of Quantitative Indicators of Enterprise Water Use Efficiency (Water-Saving China). — Calculation basis and denominator explanations for industrial water reuse rate, wastewater reuse rate, and indirect cooling water circulation rate.
- Clause Explanations of GB/T 50050—2017 and Clause Explanations of Relevant Industry Codes. — Water savings no longer increase significantly after cycles of concentration exceed 5; comparison calculation table of cycles of concentration versus makeup water and blowdown volume.
Data notes: All standard clauses cited in the text are marked with clause numbers; engineering data are taken from public reports and dissertations, and are matched item by item in the references. Where different sources are inconsistent in the basis for the same figure, the text has indicated which one is adopted in this paper. Regarding the statement on the upper and lower limits of cycles of concentration in Clause 3.1.11 of GB/T 50050—2017, two transcriptions exist in circulating versions: "should not be less than 5.0" and "should not exceed 5.0"; in engineering practice, 3.0~5.0 is generally followed. For important projects, please refer to the original text of the paper standard.
Across multiple industries nationwide (thermal power and coal chemical, papermak
Pilot to full-scale engineering (500 to 7,200 m³/d membrane-based reuse; circula