Circulating Cooling Water Cycles of Concentration: From 3 Cycles to 5 Cycles, Blowdown Down 59%, Makeup Water Down Only 16.7% — the Remaining 33% Does Not Exist Arithmetically
The cycles of concentration of circulating water are often treated as a knob that can be turned at will: when the water bill rises, turn it up two notches. But for the same 10 000 m³/h system, when N is raised from 3 to 5, the blowdown volume drops by 59.3%, while the makeup water volume drops by only 16.7%—because the 128 m³/h that evaporates is determined by the heat load, and not a single drop of it can be saved. This article uses the formulas from two national standards to work the account through to the end: N is not a knob; it is the first of three ceilings to be hit.
I. First, set out the four quantities: one identity, two boundaries
A circulating water system has only four water paths, and all water volume issues are locked down by them:
| Symbol | Meaning | Formula and Source of Values |
|---|---|---|
| E | Evaporation Loss | E = K·Δt·R, where K is the evaporation loss coefficient (1/℃), ranging from 0.0008 to 0.0016 depending on the dry-bulb temperature of the incoming air to the tower |
| W | Windage Loss | W = loss water rate × R, 0.10% with drift eliminator, 1.20% without drift eliminator (mechanical draft) |
| B | Blowdown | B = E/(N−1) − W, i.e., Clause 3.1.22 of GB/T 50102—2014 |
| M | Makeup Water | M = E + B + W, which upon combination yields M = E·N/(N−1) |
| N | Cycles of Concentration | N = M/(B+W), equivalent to N = 1 + E/(B+W) |
| T | Average Retention Time | T = V/(B+W), where V is the system holdup water volume, preferably less than R/3 |
The most important row in this table is M. Substituting B = E/(N−1) − W into M = E + B + W, W is eliminated:
M = E·N/(N−1)
In other words, the make-up water volume is determined solely by the evaporation volume and the cycles of concentration, and is independent of wind drift loss, the system holding water volume, and the blowdown volume itself. This is not a coincidence for easy memorization; it directly determines all the conclusions that follow: the room for water savings exists only in the coefficient N/(N−1) of E, and this coefficient is always greater than 1. When N = 2, it is 2.00; when N = 3, it is 1.50; when N = 5, it is 1.25; and as N→∞, it approaches 1.00.
Rewriting the same identity gives the second boundary: from N = 1 + E/(B+W), when the blowdown volume B is reduced to 0, N reaches its maximum possible value Nmax = 1 + E/W. The cycles of concentration has an upper limit set solely by wind drift loss and independent of blowdown.
II. Running the numbers on the same system: blowdown cut by nearly 60%, make-up water reduced by only one-sixth
Take the common operating conditions of a medium-sized system: circulating water volume R = 10 000 m³/h, temperature difference across the tower Δt = 8 K, summer dry-bulb temperature at the tower inlet 40 ℃ corresponding to K = 0.0016, mechanical draft tower already equipped with drift eliminators, W = 0.1%. Thus E = 128 m³/h, W = 10 m³/h. Raising N from 2 to 12, the blowdown and make-up water are calculated step by step:
| N | Blowdown B (m³/h) | Makeup Water M (m³/h) | Makeup Water Rate M/R | Blowdown Rate B/R |
|---|---|---|---|---|
| 2 | 118.00 | 256.00 | 2.56% | 1.18% |
| 3 | 54.00 | 192.00 | 1.92% | 0.54% |
| 4 | 32.67 | 170.67 | 1.71% | 0.33% |
| 5 | 22.00 | 160.00 | 1.60% | 0.22% |
| 6 | 15.60 | 153.60 | 1.54% | 0.16% |
| 8 | 8.29 | 146.29 | 1.46% | 0.08% |
| 10 | 4.22 | 142.22 | 1.42% | 0.04% |
| 12 | 1.64 | 139.64 | 1.40% | 0.02% |
From 3 times to 5 times, blowdown volume 54 → 22 m³/h, down 59.3%; makeup water volume 192 → 160 m³/h, down 16.7%. Based on 8 000 h of annual operation, both the annual water savings and the annual emission reduction are 25.6 万 m³. Both figures are correct and refer to the same thing; the difference lies in the denominator: the blowdown volume is the small remainder left after subtracting the rigid evaporation from the makeup water volume, and with a small base, the reduction rate is large; the makeup water volume includes 128 m³/h of evaporation, and with a large denominator, the reduction rate is small. The blowdown reduction rate is 3.6 times the makeup water reduction rate.

III. The lower limit of make-up water is E, so water savings have an arithmetic upper bound
In Table 1, for the expression M = E·N/(N−1), as N→∞, M→E. This is the physical lower limit of make-up water: as long as the system is dissipating heat, E must be evaporated, and not a single ton less. Therefore, for any system raised from a certain starting point N1, the proportion of make-up water that can be saved relative to the original make-up water volume has an upper bound (subtract M∞=E from M1=E·N1/(N1−1) and then divide):
Maximum water saving rate = 1/N1
| Starting point N1 | Original Makeup M1 (m³/h) | Makeup after raising to infinity (m³/h) | Maximum water saving rate on a makeup basis |
|---|---|---|---|
| 2 | 256.00 | 128.00 | 50.0% |
| 3 | 192.00 | 128.00 | 33.3% |
| 5 | 160.00 | 128.00 | 20.0% |
| 8 | 146.29 | 128.00 | 12.5% |
| 10 | 142.22 | 128.00 | 10.0% |
This table can immediately filter out a batch of promotional claims. For a plant operating long-term at around 3 times, the makeup water volume can physically be reduced by at most one third; even if the concentration ratio is raised to 8 times, 10 times, or even zero discharge, the makeup water can only be squeezed further into that 1/3. Whenever a water saving rate is reported above 50% while the starting point is 3 times, the denominator is definitely not the makeup water volume.
IV. Three Ways of Reporting the Same Retrofit: 59.3%, 16.7%, 96.4%
By presenting the discharge basis, the make-up water basis, and the low starting point together, it becomes clear how those ranges in the industry come about:
| Same Retrofit Item | Discharge Basis | Makeup Water Basis | Remarks |
|---|---|---|---|
| N 3 → 5 (existing system, only chemical dosing change required) | −59.3% | −16.7% | Annual water savings 25.6 万 m³ |
| N 2 → 10 (including side-stream demineralization retrofit) | −96.4% | −44.4% | The lower the starting point, the better the discharge basis looks |
| N 5 → 12 (electrochemical side-stream) | −92.6% | −12.7% | When the starting point is high, makeup water can hardly be reduced |
The Catalogue of Industrially Encouraged Water-Saving Processes, Technologies and Equipment (2025 年 Edition) lists electrochemical treatment of circulating water as a category for promotion and application, stating that it raises the concentration ratio to 5–12 times and can achieve a water-saving effect of 30%–80%. Comparing with the table above: if the basis is makeup water, then 5→12 is only 12.7%, and 2→10 is 44.4%; to reach 80%, two conditions must be met simultaneously: the starting point is around 2 times and the calculation is based on discharge volume. If the basis is discharge, then 30%–80% falls between 3→5 (59.3%) and 5→12 (92.6%), which is easy to achieve.
V. That W in the blowdown formula: GB/T 50102 explicitly subtracts it
The phrase most often heard on site is "blowdown = evaporation ÷ (N−1)". This phrase omits one term. The original formula given in Clause 3.1.22 of the Code for Design of Industrial Circulating Water Cooling GB/T 50102—2014 is:
Qb = [Qe − (n−1)·Qw] / (n−1)
That is, B = E/(N−1) − W. The consequences of omitting W are not minor: if the blowdown valve is set according to the formula with the missing term, the actual cycles of concentration cannot reach the design value, and the higher the target, the greater the discrepancy.
| Target N | B Set by Leakage-Type Design (m³/h) | Actual N | Makeup Water (m³/h) | Excess Makeup vs. Design Value |
|---|---|---|---|---|
| 3 | 64.00 | 2.73 | 202.00 | +5.2% |
| 5 | 32.00 | 4.05 | 170.00 | +6.2% |
| 8 | 18.29 | 5.53 | 156.29 | +6.8% |
You want to run at 5 times, but it stabilizes at 4.05 times—nearly a full tier short. And the first reaction on site when judging that "N cannot be raised" is often to add more chemicals and drain a bit more water, but neither of these will make up for W.
The same trace can also be seen in industry materials. For a 5 000 m³/h system, evaporation loss is calculated as 1.5% 75 m³/h, and wind drift loss as 0.1% 5 m³/h. The same document states that "when K is 4, the blowdown volume is approximately 75÷3=25 m³/h." However, 25 is the result of omitting W: the true B should be 25−5=20 m³/h. If the valve is set according to B=25, the system actually runs at 105÷30=3.50 times, not 4 times; to reach 4 times, the blowdown must be reduced to 20. The same document had just stated earlier that the wind drift loss is 5 m³/h, but then dropped it when calculating blowdown.
Another type of summary table does the opposite, folding W into the blowdown volume. A water conservation document for a certain refining and chemical enterprise provides data for a 10 000 t/h system: N is raised from 3.0 to 5.0, makeup water 166 → 138 t/h (−16.9%), blowdown 56 → 28 t/h (−50%). The evaporation volume implied by this set of numbers is 166−56=110 t/h and 138−28=110 t/h, which are completely consistent across the two levels, indicating that W is recorded as zero (or merged into blowdown). If W=10 t/h is listed separately according to 0.1%, the two sets of numbers yield 2.52 and 3.63 times, neither of which matches the 3.0 and 5.0 in the table header. When reading this type of table, the first thing to do is confirm which column W is in.
VI. The Other Side of W: The Upper Limit of Cycles of Concentration Is 1+E/W
Table 3.1.21 of the Code for Design of Industrial Circulating Water Cooling GB/T 50102—2014 specifies the wind drift loss rate very rigidly: mechanical draft towers with drift eliminators 0.10%, without drift eliminators 1.20%; natural draft towers with drift eliminators 0.05%, without drift eliminators 0.80%. Whether there is a drift eliminator makes a difference of 12 times.
Substituting W into Nmax = 1 + E/W, for the same system with E=128 m³/h, the upper limit of cycles of concentration is independently locked by W:
| Tower Type and Configuration | W/R | W (m³/h) | Upper Limit of N (B→0) |
|---|---|---|---|
| Natural Draft Tower with Drift Eliminator | 0.05% | 5 | 26.6 |
| Mechanical Draft Tower with Drift Eliminator | 0.10% | 10 | 13.8 |
| Mechanical Draft Tower with Partially Failed Drift Eliminator (calculated as 0.5%) | 0.50% | 50 | 3.56 |
| Natural Draft Tower without Drift Eliminator | 0.80% | 80 | 2.60 |
| Mechanical Draft Tower without Drift Eliminator | 1.20% | 120 | 2.07 |
The conclusion is somewhat counterintuitive: For a mechanical draft tower without drift eliminators (or with drift eliminators that are damaged, clogged, or removed), no matter how small the blowdown valve is closed, the cycles of concentration cannot reach 3. In this case, if operated at B=54 m³/h per Table 2, the actual cycles can only reach 1.74, the makeup water increases from 192 to 302 m³/h, an additional 57.3%. The symptom observed on site is "N never goes up, and the water bill stays high," and the usual remedy is to increase blowdown—but increasing blowdown only makes N even lower.
VII. E is not a constant either: the evaporation coefficient doubles with the dry-bulb temperature difference
K in E = K·Δt·R is not a single number of 0.16%/℃. Taking values according to the dry-bulb temperature at the tower inlet, K ranges from 0.0008 at −10 ℃ to 0.0016 at 40 ℃, exactly a factor of two. With the same blowdown valve opening (B=54 m³/h) and the same tower:
| Inlet Dry-Bulb Temperature (℃) | K (1/℃) | E (m³/h) | Makeup Water M (m³/h) | Actual N at Same Valve Setting |
|---|---|---|---|---|
| −10 | 0.0008 | 64.0 | 128.0 | 2.00 |
| 0 | 0.0010 | 80.0 | 144.0 | 2.25 |
| 10 | 0.0012 | 96.0 | 160.0 | 2.50 |
| 20 | 0.0014 | 112.0 | 176.0 | 2.75 |
| 30 | 0.0015 | 120.0 | 184.0 | 2.88 |
| 40 | 0.0016 | 128.0 | 192.0 | 3.00 |
Two consequences. First, the cycles of concentration will automatically drop in winter—not because water quality has improved, but because evaporation is lower and makeup water is lower, while the blowdown valve has not been adjusted. In winter, N drops from 3.00 to 2.00, and the overall salt concentration shifts downward: scaling risk decreases while corrosion risk increases (low alkalinity, low pH, and weak buffering capacity against dissolved salts). This is another type of risk, not "safer." Second, if the annual water balance is calculated using the summer K, it will be overestimated by more than 30%: if weighted by 3 months at 0.0016, 3 months at 0.0008, and 6 months at 0.0012, the annual average K = 0.0012, E = 96 m³/h; using 0.0016 to calculate the full year, the annual evaporation is overestimated by 0.0016/0.0012−1 = 33.3%, and the annual makeup water is overestimated by the same proportion. If the payback period of a water-saving retrofit is based on this figure, it will be underestimated by one third.
Also correct a more commonly misunderstood inference: raising the temperature difference saves pump energy, not water
The same sentence appears repeatedly in industry materials—"Increase the supply-return temperature difference of circulating water, raising the temperature difference to about 8 ℃." This statement is correct, but what it saves is not water. For a fixed heat load Q, the circulating water volume is inversely proportional to the temperature difference (R=Q/(c·ρ·Δt)), while evaporation is determined only by the heat load: substituting R in E=K·Δt·R, Δt cancels out, giving E=K·Q/(c·ρ)—evaporation is independent of the temperature difference. Therefore, make-up water M=E·N/(N−1) is also independent of the temperature difference.
So what does raising the temperature difference actually change? It only changes W: W=0.1%×R, with R dropping from 16 000 to 10 000, and W dropping from 16 to 10. To maintain the same N, B must be increased from 48 to 54—water shifts from the windage loss column to the blowdown column, make-up water is not reduced by a single ton (both are 192 m³/h), while the circulating water volume drops by 37.5%; what is saved is pump power consumption. Making this point clear is very useful: when someone reports "raising the temperature difference from 5 ℃ to 8 ℃" as a water-saving achievement, the water savings figure should be filled in as 0, and only the electricity savings figure can be substantiated.
VIII. The second ceiling: chemical residence time, N = 1 + E·T/V
Clause 3.2.1 of GB/T 50050—2017 is a mandatory design constraint: the design residence time of circulating cooling water in an open system shall not exceed the allowable residence time of the chemicals, T = V/(B+W); GB 50648—2011 likewise emphasizes this point and notes that the allowable residence time is usually provided by the chemical supplier. Combining T = V/(B+W) with N = 1 + E/(B+W), W and B cancel out together:
N = 1 + E·T/V
Taking the upper limit V=R/3=3 333 m³, E=128 m³/h from Clause 3.2.2 of GB/T 50050, the slope E/V=0.0384 1/h, thus N = 1 + 0.0384·T. This straight line directly translates "how long the chemicals can soak" into "how many cycles of concentration can be reached":
| Allowable Retention Time T (h) | Corresponding Upper Limit of N | Which Generation of Chemicals This Tier Corresponds To |
|---|---|---|
| 50 | 2.92 | Polyphosphates (P−O−P bonds hydrolyze readily; the hydrolysis product is orthophosphate, which forms calcium phosphate scale with calcium that is more difficult to treat) |
| 100 | 4.84 | Organic phosphonates (HEDP, ATMP; C−P bonds are stable) |
| 150 | 6.76 | Organic phosphonate + polymer blend |
| 200 | 8.68 | Upper limit range of blended formulations |
| 300 | 12.52 | Nominal values for modern composite chemicals |
This column explains how the "3 times" figure is derived.It is not calculated from scaling; it is calculated from 50 h: polyphosphates hydrolyze and lose effectiveness after soaking in the system for 50 h, and a conventional system with V/R=1/3 and E/R≈1.28% corresponds to N=1+0.0384×50=2.92. In other words, N≈3 is a physical constant of the phosphorus-based chemical era, not a water quality constant. The statement in industry literature that "the cycles of concentration for phosphorus-based water treatment are generally around 3; this 3 is actually intended to control the chemical retention time to no more than 50 h" refers to exactly this.
For the same system, the actual residence time according to Table 2 is: 52.1 h at N=3, 104.2 h at N=5, 182.3 h at N=8, and 286.5 h at N=12. Thus three things hold true simultaneously:
- To stabilize at 5 times, the allowable residence time for the chemicals must be ≥105 h—organophosphonates and compounded formulations are sufficient, but polyphosphates are not. This corresponds exactly to GB/T 50050—2017 raising the design cycles of concentration from "around 3" to "not less than 5.0";
- To achieve 8 times (water efficiency guidelines for the steel industry in some provinces have already proposed 8 times or more), the corresponding value is 182 h, and the chemicals must be selected according to the 200 h tier;
- 12 times corresponds to 287 h, which is already at the upper limit of the nominal 300 h for modern composite chemicals—if pushed any higher, what gets stuck is not the salt, but the shelf life of the chemicals.
There is also a design blind spot here that is hardest to discover during the operation phase. B appears in the denominators of both N and T, and acts in opposite directions: reducing B increases N and also increases T—the hand that wants to save water is simultaneously pushing the chemicals toward extended service beyond their limits. Therefore, for "wanting both high N and short T," the only variable that can be adjusted is V (holdup volume), not B. The V/R ratio of old systems is often 1:2 or even larger (Article 3.2.2 of GB/T 50050 requires it to preferably be less than 1/3). Taking V=5 000 m³, at N=5, T=5 000/32=156.3 h, which has already exceeded the allowable value for some organophosphonate formulations; to reduce it to 100 h, V must be lowered below 3 200 m³. The approach is to clear dead corners, reduce tank volume, and cut off branch pipes that have not flowed for a long time—none of these three things cost money, but they never appear in water-saving retrofit plans.
IX. The first ceiling: salt, N ≤ 1100/(calcium hardness + alkalinity)
Article 3.1.10 of GB/T 50050—2017 stipulates: when the sum of calcium hardness and total alkalinity in indirect open cooling and direct cooling systems is greater than 1 100 mg/L (calculated as CaCO3), or when the stability index RSI is less than 3.3, sulfuric acid should be added or softening treatment should be carried out. This limit gives the "sum"; dividing it by the sum value of the make-up water itself gives the maximum cycles to which this water can be concentrated:
| Make-up Water Calcium Hardness (mg/L, as CaCO3) | Make-up Water Total Alkalinity | Sum of the Two | Upper Limit of N | Typical Water Source |
|---|---|---|---|---|
| 60 | 50 | 110 | 10.00 | Soft water in southern China, some reservoir water |
| 80 | 60 | 140 | 7.86 | Surface water in the middle and lower reaches of the Yangtze River |
| 100 | 80 | 180 | 6.11 | Surface water of relatively good quality |
| 120 | 100 | 220 | 5.00 | Just enough for 5 times |
| 150 | 120 | 270 | 4.07 | High-hardness, high-alkalinity groundwater in North and Northwest China |
| 200 | 150 | 350 | 3.14 | Deep groundwater, some karst water |
Chloride is the second constraint, usually not the first, but it can overtake at coastal and high-chloride make-up water locations: carbon steel and stainless steel equipment with water on the tube side is limited to 1 000 mg/L; stainless steel equipment with water on the shell side (wall temperature ≤70 ℃, outlet water <45 ℃) is limited to 700 mg/L; direct-cooled rolled steel laminar flow is even stricter at 300 mg/L. Based on make-up water Cl⁻ of 30 mg/L, the three tiers correspond to 33.3, 23.3, and 10.0 times respectively; if the make-up water Cl⁻ has already reached 80 mg/L, only 8.8 times remain for the 700 mg/L tier.
The minimum of the three ceilings is the true value of N. Taking the above North China makeup water as an example again: salinity gives 4.07, chemicals (tier 200 h) give 8.68, and a normally functioning drift eliminator gives 13.8—the shortest stave in the barrel is salinity. GB/T 50050—2017 states "should not be less than 5.0, and shall not be less than 3.0"—the gap between these two terms is exactly where this group of plants sits: they cannot achieve 5.0, but 3.0 is the bottom line. To truly reach 5 times, salinity must be addressed first—adding sulfuric acid to knock down alkalinity, or softening/desalinating the makeup water—rather than switching to a chemical supplier that excels at high cycles of concentration.
10. The Same Basin of Water, Four Measurement Methods, Four N Values
The definition of cycles of concentration depends on "a certain component that does not leave with the water volume," and which component is chosen changes the result. Let the true value N = 5.0, makeup water Cl⁻ 40 mg/L, makeup water conductivity 520 μS/cm, makeup water calcium hardness 120 mg/L:
| Determination Method | Reading | Back-calculated N | Deviation | Source of Deviation |
|---|---|---|---|---|
| Chloride ratio (baseline method) | 200 ÷ 40 mg/L | 5.00 | 0 | Cl⁻ does not precipitate or biodegrade; however, chlorine-based biocides introduce additional Cl⁻ |
| Potassium ion ratio | 20 ÷ 4.0 mg/L | 5.00 | 0 | Not subject to chlorination interference; requires atomic absorption or ion chromatography |
| Conductivity ratio | 3 200 ÷ 520 μS/cm | 6.15 | +23.1% | Acid addition and chemicals contribute approximately 600 μS/cm |
| Calcium hardness ratio | 552 ÷ 120 mg/L | 4.60 | −8.0% | Calcium has precipitated 8%, reducing the numerator |