Cases

Cases

Cases
Chlor-alkali water: total mercury 3 μg written at the workshop outlet, the water route only accounts for 4 per ten thousand.
Chlor-alkali industr
Chlor-alkali water: total mercury 3 μg written at the workshop outlet, the water route only accounts for 4 per ten thousand.
Nationwide across multiple industries (chlor-alkali, calcium carbide process PVC
Engineering (mercury-containing wastewater 10 to 120 m³/h; caustic soda 100,000
GB 15581—2016 lists 14 water pollutants for the caustic soda and polyvinyl chloride industries, of which 4 are sampled at the workshop outlet regardless of direct or indirect discharge, and none of these 4 values has been changed in the special emission l
View Details
Reclaimed Water Reuse Rate: Within the same plant, both 99% and 16.7% can be correct—the difference lies in the denominator.
Reclaimed Water Reus
Reclaimed Water Reuse Rate: Within the same plant, both 99% and 16.7% can be correct—the difference lies in the denominator.
Across multiple industries nationwide (thermal power and coal chemical, papermak
Pilot to full-scale engineering (500 to 7,200 m³/d membrane-based reuse; circula
The reuse rate has five denominators, and the same water stream in the same plant can yield four different figures: 99.0%, 95.3%, 40.0%, and 16.7%. The ceiling on the concentration factor is not scaling but wind drift loss; once N exceeds it, no water can
View Details
Biodegradability: the B/C 0.3 line measures oxygen consumption over five days, not whether microorganisms can handle it.
Water Quality Analys
Biodegradability: the B/C 0.3 line measures oxygen consumption over five days, not whether microorganisms can handle it.
Across multiple industries nationwide (fine chemicals and pharmaceuticals, texti
From laboratory methodology to engineering application (BOD5 measurement range 2
The numerator of B/C is the five-day oxygen consumption, while the denominator is the two-hour chemical oxidation amount—the two are not the same yardstick. For the same BOD5 of 200 mg/L, the back-calculated BODu can range from 231 to 904, a 3.9-fold diff
View Details
Equalization Tank: Equalizing flow requires only 4.5 hours, while equalizing quality requires 38 hours; 8 hours achieves neither.
Equalization Tank an
Equalization Tank: Equalizing flow requires only 4.5 hours, while equalizing quality requires 38 hours; 8 hours achieves neither.
Across multiple industries nationwide (leather and fur processing, slaughtering
Pilot to full-scale engineering (tens to tens of thousands of m³/d; effective vo
GB 50014 only states that equalization facilities should be provided, without giving a volume calculation method; six industry standards offer six sets of figures ranging from 4 to 24 hours. Treating the equalization tank as a first-order system: an 8-hou
View Details
Anaerobic reactor: the upper limit in Table 1 of the main text is 8, and the average in Appendix A is 9.96.
Anaerobic biological
Anaerobic reactor: the upper limit in Table 1 of the main text is 8, and the average in Appendix A is 9.96.
Multi-industry nationwide coverage (alcohol and fuel ethanol, beer, citric acid,
Pilot to full-scale engineering (hundreds to 15,000 m³/d; effective reactor volu
In the same UASB specification, the upper limit of granular sludge loading in Table 1 of the main text is only 8 kgCOD/(m³·d), while in Appendix A, 27 of the 34 categories of wastewater have averages exceeding 8, with a mean of 9.96 and a maximum of 17.8.
View Details
At the plant boundary: hydrogen sulfide outside the wall must not exceed 0.06, which is 1/167 of the workshop limit.
Plant boundary envir
At the plant boundary: hydrogen sulfide outside the wall must not exceed 0.06, which is 1/167 of the workshop limit.
Nationwide multi-industry coverage (municipal wastewater treatment plants, centr
Pilot to full-scale engineering (hundreds to 140,000 m³/d; plant boundary ammoni
For the same hydrogen sulfide, the limit inside the workshop is 10 mg/m³, while outside the perimeter wall it is only 0.06 — a 167-fold difference. And on the outside of the perimeter wall, three other figures sit side by side: odor concentration 20 (dime